Add to Cart
Cube Fire Test Chamber Safety Protection Standard Bs 6401 Universal Laboratory Testing
Standard: ISO5659-2 ASTM E662 BS 6401 GB/T 8323
• ASTM E 662 : Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials
• BSI 6401 : British Standard Method for Measurement, in the laboratory, of the specific optical density of smoke generated by materials
• ISO 5659-2 : Plastics-Smoke generation -Part 2: Determination of optical density by a single-chamber test
• NES 711 : Determination of the Smoke Index of Products of combustion from Small Specimens of Material
Technical data :
1.) All the Inside&outer of the container are Teflon coated,can resist etchant gas to increase the life of machine;
2.) the machine are all opened designed
3.) install assistant heating device in the outer of the tester ,it can set temperature according to different standard requirements,so can shorten the temperature balance time of container;
4.) install the aluminum explosion-proof in the container to avoid the life risk;
5.) open the gas pressure release on top of container,connect with the pressure adjust flask,can adjust the pressure automatically ;
6.) install automatic air-cylinder in both top and bottom of container,it will be convenient for user;
7.) provide ASTM E662 all-radiant furnace,can provide 25kw/m2 heat radiation output;
8.) provide ASTM E662 standard naked light burner,can work with all-radiant furnace to do naked light burning test;
9.) provide air-cooled copper calorimeter,can use back cooling mode to adjust it’s surface temperature when do the test;
10.) provide ISO 5659-2/GB/T8323 radiation cone device,can provide 50kw/m2 heat radiation output;
11.) provide ISO 5659-2/GB/TB323 standard naked light burner,can work with radiation cone to do naked light burning test;
12.) provide America MED THERM water cool heat flow meter(cone calorimeter),provide the measurement certificate which can date back to America NIST;
13.) provide self circulating cooling water,it’ll be convenient for user;
14.) provide weighing device,can do MOD smoke density test and do heat weightless test;
15.) the range of sensor is 0-5000g,the precision is 0.01g;
16.) provide NES 711 naked light burner and whisk fans
17.) adopted air joint connection between all-radiation furnace and radiation cone ,user just need to insert or pluck then can make the change ;
18.) install optical cassette on the top of container,side window photomultiplier for light source acceptance,s-4 rate respondtransmission accuracy can reach 0.0001%;
19.) install wheelrotation device in the cassette ,can automatically change CLEAR/FILTER/DARK according to smoke density transformation;
20.) install ND2 neutral filter in cassette,it will convenient for users self-adjust also can use for automatic change tab in test;
21.) under the container is filament lamp,can provide even light spot output;
Main configure:
1.)17inch touch control computer main engine
2.America NI software design platform
3.)Import heat flow
4.)Import electrical control part
5.)Import temperature sensor
6.)Sus 304 stainless steel porcelain enamel processing
7.)RAL9002 standard colour paint on outer container
Size | 914*914*610mm |
Standard | ISO5659-2,ASTM E662 |
Material | Sus304 stainless steel |
Main engine | 17inch touch control computer |
Flow meter | Imported flow meter |
sensor | Import temperature sensor |